What is the rod distance required by the NEC away from the electrical panel?

What is the rod distance required by the NEC away from the electrical panel?  - E&S Grounding Ask the Experts

Greg Asked:
In order to place two grounding rods, what is the distance required by the NEC away from the electrical panel? And what is the distance they should be from each other (the rods)?

New call-to-action

Our Answer:
The National Electrical Code (NEC) Article 250 does not have a requirement for how far the grounding rod needs to be placed in relation to the electrical panel.  Generally speaking “best practice” would indicate that the closer you install the rod to the panel, the better.  Now, if you are installing the grounding rod really far away, the NEC may require you to increase the conductor size to ensure that you don’t have an impedance issue. 

That said, it is becoming quite common for local governing authorities (building inspectors), to issue rules requiring the installation of grounding rods within some specified distance from the panel.  We think this is a good idea for a number of reasons.  While it may be difficult (or unsightly) to install a ground rod near the panel, as you may need to core through some concrete, the advantages of proximal grounding outweigh the effort.  Remember, if you do core through concrete, you must install a PVC sleeve to prevent accidental contact between the rod and any rebar in the slab.

As far as spacing of the grounding electrodes goes, NEC 250.53 (B) requires a minimum of 6-ft between electrodes.  However, in NEC 250.56 they note that spacing’s greater than 6-ft will improve the efficiency of the electrode.  The spacing of electrodes deals with a theory known as the Sphere of Influence.  Basically you want to space your electrodes out 2-times (2X) the length of the electrode.  So, if you are installing 10-ft grounding rods, you would want them spaced at 20-ft intervals. 

 

Let's Talk! Schedule a FREE Phone Consultation Today.

Wherever you're located, learn how good a fit we are for your project.

 

nec, electrode system, electrode, Grounding & Earthing Below-Grade Electrodes, electrical panel, PVC, rods, sphere of influence

Related Posts

What other types of grounding electrodes are there apart from ground rods? - E&S Grounding Ask the Experts

What other types of grounding electrodes are there apart from...

Read More
What is Step and Touch Potential and Reducing Resistance To Ground? - E&S Grounding Solutions

What is Step and Touch Potential and Reducing Resistance To...

Step Potential Step potential is the step voltage between the feet of a person standing near an energized grounded object. It is equal to the difference in voltage, given by the voltage distribution...

Read More
Applying salt around earthing electrodes to help resolve neutral to ground line voltage issues - E&S Grounding Ask the Experts

Applying salt around earthing electrodes to help resolve neutral...

Vighnesh asked:Our neutral to earth voltage is fluctuating from 2.5v to 4.5v. We have a separate neutral earthing for UPS and DG and separate body earthing. We also regularly applying salt for earth...

Read More
Will applying salt around earthing electrodes help to resolve neutral to ground line voltage issues? - E&S Grounding Ask the Experts

Will applying salt around earthing electrodes help to resolve...

Vighnesh asked:Our neutral to earth voltage is fluctuating from 2.5v to 4.5v. We have a separate neutral earthing for UPS and DG and separate body earthing. We also regularly applying salt for earth...

Read More