Rebar Grounding & Bonding: NEC Requirements Explained

Jake Asked:
What are the NEC Requirements for Grounding and Bonding Rebar?

 

Our Answer:
The National Electrical Code (NEC) requires that all normally non-current-carrying metallic objects in a given structure be bonded together to form a single common system that is at the same potential. This includes the steel rebar in the concrete foundations. We see in Article 250.50 the mandate that all electrodes listed in the code (steel rebar in concrete can sometimes qualify as an electrode) be bonded together, whether they are used as an electrode or not.

In the case of steel rebar in concrete, we see in 250.52(A)(3)(Information Note) that epoxy coated rebar and/or a vapor barrier can negate our ability to use the rebar as an electrode, however our mandate to bond the systems to form a common system still remains under 250.50. In other words, you must bond the steel rebar in concrete foundations whether you use it as an electrode or not (just like a water pipe, gas pipe, alarm system, fire sprinklers, CATV, Telco, etc).

Please see the NEC 2017 Handbook Exhibits: 250.22, 250.23, 250.29, and 250.30.

Many people are concerned that bonding the steel rebar in concrete may lead to cracking of the concrete due to thermal heating. It is a very counterintuitive concept, but it’s actually the exact opposite. We also see hesitation when people are instructed to bond their gas pipes to the grounding and lightning systems (NEC 250.104(B), 250.52(B)(1), and NFPA 54 Section 7.13) as well. Note: Lightning systems must be bonded per NEC 250.106, 250.4(A)(1), 250.4(B)(1), and NFPA 780 Section 4.14. By removing the difference in potential, we remove the electrical risk.

If we do not bond the rebar in concrete, we generate a difference in potential between the concrete and the bonding metal objects inches above, which will allow arc-flash to occur, which will cause severe damage. Consider the lightning protection system requirements to bond metal window flashing to a down conductor so as to prevent arc-flash.

Please see NFPA 780-2014 Sections 4.9.13, 4.13.3, and 4.19 for more information regarding bonding steel rebar.

 

New call-to-action

 

Note that concrete is an electrically conductive medium, typically ranging between 30 to 200 ohm meters (See IEEE Std. 80-2013 Section 14.6), so arc-flash between objects with differences in potential is a dangerous and real concern.

In your case, your steel rebar has a copper ground loop at the very bottom of the system. Any hazardous currents that enter the copper wire will want to stay on the copper component and go into the earth through the easiest path. By bonding the steel rebar you simply eliminate the difference in potential between the metal objects above the steel rebar and the steel rebar, you are not forcing current to travel through it to find a path to ground. Hazardous currents have a path to ground, the massive buried copper network and grounding electrodes. Remember, copper is 12 to 17 times more conductive than steel and is additionally 250 to 6,000 times less magnetic. In fact, copper is diamagnetic. Meaning that the steel is high-impedance in relation to the copper.

In addition, we have to consider IEEE Standard 80 and human safety. The steel rebar in the concrete IS THE SAFETY MAT for eliminating hazardous step and touch voltages. It MUST be bonded. If the steel rebar is not bonded, you would need to install a copper grounding grid under the workers feet in order to keep them safe. You may want to contact whoever did the mandatory OSHA 29 CFR 1910.269 App C Step & Touch analysis and see what they have to say about workers walking on top of concrete pads with un-bonded steel rebar. They will not be happy. Please see IEEE Standard 80-2013 Section 14.6. You may also want to consider looking at (Canadian) CEC Rule 36-304 and Figure 36-11, which is in full compliance with the NEC and IEEE 80, and very clearly spells out the mandatory steel rebar bonding, with illustrations and code.

We additionally see requirements for bonding steel rebar in concrete in IEEE 1100 (Emerald Book) Section 8.5 and IEEE 142 (Green Book) Section 4.2.1 and 4.2.3. Magnetic build up, harmonics, transients, EMI/EMF and other objectionable currents that can build up on steel rebar will need a path to ground. Moreover, have a number of sensitive electronics systems on site. Please see Motorola’s R56 standard, ATT-TP-76416 standard, and ANSI/TIA/EIA-J-STD-607-C for additional steel rebar bonding requirements related to the data communication systems. Finally, we can see a list numerous standards from the International Electrotechnical Commission (IEC) which would additionally agree with the requirements to bond steel rebar in your electrical system.

 

Let's Talk! Schedule a FREE Phone Consultation Today.

Wherever you're located, learn how good a fit we are for your project.

 


nec, Grounding & Earthing Below-Grade Electrodes, Grounding & Earthing Applications, concrete, rebar, Ufer ground, IEC

Related Posts

Can all steel rebar be welded? - E&S Grounding Ask the Experts

Can all steel rebar be welded?

Jeff asked:Can I weld any steel rebar or are there specific grades to look for?Our Answer:Not all rebar can be welded, particularly with the exothermic welding process as it must be able to heat the...

Read More
What Is Electrical Grounding? - E&S Grounding Solutions

What Is Electrical Grounding?

What Is Electrical Grounding? Electrical grounding or “Grounding” originally began as a safety measure used to help prevent people from accidentally coming in contact with electrical hazards. Think...

Read More
What are some different types of grounding electrodes? - E&S Grounding Solutions

What are some different types of grounding electrodes?

Grounding is the process of electrically connecting any metallic object to the earth by the way of an earth electrode system. The National Electric Code requires that the grounding electrodes be...

Read More
Will applying salt around earthing electrodes help to resolve neutral to ground line voltage issues? - E&S Grounding Ask the Experts

Will applying salt around earthing electrodes help to resolve...

Vighnesh asked:Our neutral to earth voltage is fluctuating from 2.5v to 4.5v. We have a separate neutral earthing for UPS and DG and separate body earthing. We also regularly applying salt for earth...

Read More