When did the NEC Decide the Neutral and Ground Have to be Separated at the Panel?

When did the NEC Decide the Neutral and Ground Have to be Separated at the Panel? - E&S Grounding Ask the Experts

Karl Asked:
In what year did the NEC first require that the neutral and ground have to be separated in a sub panel?

Our Answer:
Grounding and earthing, or specifically, that the earth will act as an electrical conductor has been known for over 270 years.  We have white papers dating back to 1746 describing the phenomena, and of course, Benjamin Franklin used grounding for his lightning protection systems in 1749.

We also have papers in 1803 and 1808 requiring the earthing of battery systems, and of course starting 1882 Thomas Edison mandating the grounding of his systems worldwide (including the separation of the return current conductor “ie neutral” from the grounding system).

The first code regarding mandatory grounding (and separation from the neutral) goes back to the American Institute of Electrical Engineers (AIEE) in October of 1884 where they stated in their “Transactions” publication: “there is no element or adjunct of electrical science more important in many respects then the terrestrial ball itself, when we consider it in its relationship to the electrical circuit…”

The NFPA issued its first requirement for grounding conductors that are separate from the neutral in March of 1896, with the NEC following up in 1897.  Note: the NEC was not part of the NFPA umbrella until 1911.

So in answer to your question, the NEC has required the separation of the neutral from the ground since its very first publication in 1897.

Please refer to this article on when and where to make neutral-to-ground bonds, and possibly even more importantly, when NOT to make such bonds.

The Engineering Experts at E&S Grounding Solutions

grounding, Bonding Above-Grade Grounding & Earthing Systems, neutral-to-ground, Neutral and Ground separation, Benjamin Franklin, sub panel, History, Thomas Edison

Related Posts

Will applying salt around earthing electrodes help to resolve neutral to ground line voltage issues? - E&S Grounding Ask the Experts

Will applying salt around earthing electrodes help to resolve...

Vighnesh asked:Our neutral to earth voltage is fluctuating from 2.5v to 4.5v. We have a separate neutral earthing for UPS and DG and separate body earthing. We also regularly applying salt for earth...

Read More
Beware of the NFPA 780 Simplified Lightning Risk Assessment - E&S Grounding Solutions

Beware of the NFPA 780 Simplified Lightning Risk Assessment

The de facto standard for Lightning Protection in the US is NFPA 780: Standard for the Installation of Lightning Protection Systems. Its Lightning Risk Assessment tool can be found in NFPA 780 Annex...

Read More
Do I need a grounded conductor in my subpanel if all my loads are all 220v? - E&S Grounding Ask the Experts

Do I need a grounded conductor in my subpanel if all my loads...

Jack Asked:Do I need a grounded conductor (neutral) in my subpanel if all my loads are all 220v (i.e. 2-phase)?

Read More
When to Bond Neutral to Ground in Electrical Panels - E&S Grounding

When to bond neutral and ground? Should you make...

John asked:Should you make neutral-to-ground bonds in electrical panels?

Read More