What is the difference between neutral and ground wires?

What is the difference between neutral and ground (PE) wires?

Raymond asked:
What is the difference between neutral and ground wires?

 

Our Answer:
Let’s start by getting the terminology down:

  • The neutral wire or “grounded conductor” is a normally current-carrying conductor, similar in many ways to a phase wire in that it will carry the same amount of current in single phase system.  It is grounded (connected to the earth) at the center-tap point of transformer for a number of very complex reasons.  The neutral conductor is isolated from accidental contact because it is a very dangerous normally current carrying conductor.
  • The ground wire is a normally non-current carrying conductor, designed to carry the electrical energy should a fault occur.  This normally non-current carrying conductor is also bonded to every exposed metallic part in your structure, to ensure that there are no hazardous differences in potential on the objects you touch.  You should be able to touch exposed ground wires with no concern, although all exposed wires should always be treated as live and dangerous.
    New call-to-action

The reason for the neutral wire is to carry electrical currents back to the transformer during normal operations, in a manner that keeps those hazardous electrical currents away from people and exposed metal objects.

The reason for the ground wire is to eliminate any differences in potential on the exposed metal objects you might touch, and to carry return currents back to the transformer in case of an electrical fault (the unintentional contact of electrical currents to exposed metal objects).

In regards to the grounding electrode connection, a simple receptacle tester would not detect the presence of a ground rod, it only checks to see if the ground spade of the outlet is in an open condition (high resistance).

Of interest is that your electrical system should function safely even if your entire structure were lifted into space.  The physical grounding wires would ensure that your electrical circuit breakers would still trip, even if you had no grounding rods and were not connected to the earth at all.  The reason for the ground connection has to do with the needs of your local utility company, and a need to remove stray harmonics and other forms of objectionable current.

In the International Electrical Code (IEC) they call a ground wire a “Protective Earth” or PE.  The Neutral is called a “Neutral” or N.  When the power company only brings over normally current carrying wires (phase and neutral only), they call the neutral wire a “PEN conductor”, because it is both a Protective Earth (PE) AND a Neutral (N).  They define this type of electrical system as a “Combined” or C.  Meaning that the neutral and protective earth is Combined.  When you split the neutral and PE into two separate entities, they call it a Separated or S system.  When the power company bring over a PEN conductor and you split it into two in your electrical cabinet, they call that electrical system a C-S, or “Combined then Separated” system.

 

The Engineering Experts at E&S Grounding Solutions

 

Let's Talk! Schedule a FREE Phone Consultation Today.
Wherever you're located, learn how good a fit we are for your project.

 


ground wire, Bonding Above-Grade Grounding & Earthing Systems, neutral-to-ground, Neutral and Ground separation, electrolytes, terminology, conductors, Neutral wire

Related Posts

Why separate the ground bar from the neutral bar in a sub-panel? - E&S Grounding Ask the Experts

Why separate the ground bar from the neutral bar in a sub-panel?

Russ asked: How can I correctly separate the ground bar from the neutral bar in an electrical sub-panel?The Answer:

Read More
Do I need a grounded conductor in my subpanel if all my loads are all 220v? - E&S Grounding Ask the Experts

Do I need a grounded conductor in my subpanel if all my loads...

Jack Asked:Do I need a grounded conductor (neutral) in my subpanel if all my loads are all 220v (i.e. 2-phase)?

Read More
When did the NEC Decide the Neutral and Ground Have to be Separated at the Panel? - E&S Grounding Ask the Experts

When did the NEC Decide the Neutral and Ground Have to be...

Karl Asked:In what year did the NEC first require that the neutral and ground have to be separated in a sub panel?

Read More
Shared Neutral for 120/208V, 3-Phase, 4-Wire Feeders

Shared Neutral for 120/208V, 3-Phase, 4-Wire Feeders

Bob asked:How many ”hot” wires can a single neutral support?

Read More