
Lightning Protection Down Conductor Size Requirements | NFPA 780 Standards
What is the minimum size of a down conductor for lightning protection? Per NFPA 780, stranded copper conductors must be at least 57,400 circular mils (187 lbs/1000 ft). Aluminum conductors must be at least 98,600 cir. mils (95 lbs/1000 ft). Secondary and bonding conductors require a minimum of 26,240 cir. mils for copper and 41,100 cir. mils for aluminum.
Lightning Protection Down Conductor Size Requirements
What is the minimum size of a down conductor for lightning protection? The following conductor sizing requirements are specified under NFPA 780 (Standard for the Installation of Lightning Protection Systems):
Primary Down Conductors (Copper) Stranded copper conductors shall be at least 57,400 circular mils at 187 lbs per 1,000 ft.
Primary Down Conductors (Aluminum) Aluminum conductors shall be at least 98,600 cir. mils at 95 lbs per 1,000 ft.
- Secondary and Bonding Conductors
- The minimum size for secondary or bonding conductors shall be:
- Copper: 26,240 cir. mils
- Aluminum: 41,100 cir. mils
- Heavy-Duty Primary Conductors
- For heavy-duty applications, primary conductors shall be not less than:
- Copper: 115,000 cir. mils at 375 lbs per 1,000 ft
- Aluminum: 192,000 cir. mils at 190 lbs per 1,000 ft
- Secondary bonding conductors for heavy-duty applications:
- Copper: 26,240 cir. mils
- Aluminum: 41,100 cir. mils
What is the Individual Resistance of a Grounding Electrode?
The individual resistance of a grounding electrode depends on soil resistivity, electrode length, and electrode diameter. For a single ground rod, the resistance to earth is calculated using the Dwight formula. Typical values range from 5 ohms to over 100 ohms depending on soil conditions.
What is the Combined Resistance of Parallel Electrodes?
When multiple electrodes are connected in parallel, the combined resistance is not simply the individual resistance divided by the number of electrodes. Due to the mutual interference between electrodes, the combined resistance is higher than a simple parallel calculation would suggest. The combined resistance of N electrodes in parallel is approximately: R_combined = R_individual / N × (1 + (mutual resistance factor))
For design purposes, the NEC requires that the grounding electrode system achieve a resistance to ground of 25 ohms or less. If a single electrode does not achieve 25 ohms, a supplemental electrode must be added.
What is the Resistance of a Lightning Protection Ground System?
For lightning protection systems, NFPA 780 requires that the resistance to ground of the grounding system be as low as practicable. A resistance of 10 ohms or less is considered excellent. The resistance is measured using the fall-of-potential method or the clamp-on method for active systems.
Related Articles

A Critical Review of Lightning ProtectionSystems: Science, Standards, and Safety
1. Electromagnetic Pulse (EMP) Damage. 2. Ground Reference Potential Change Damage. 3. Strikes to Power and Data Lines Causing Surges.
Read article
Lightning Protection for Substations: NFPA 780 vs. IEC 62305
A comparison of the two primary lightning protection standards — NFPA 780 and IEC 62305 — and guidance on which standard to apply for substation lightning protection design.
Read article
Does a Lightning Protection System Attract Lightning Strikes?
There is a persistent myth that installing a lightning protection system on a structure will increase the likelihood of that structure being struck and damaged, however, this is simply not true.
Read article